PROTEGRA CS® RO/EDI

Consistently high water quality without the use of chemicals
​The reverse osmosis Protegra CS® RO/EDI systems are designed to serve the need for high volumes of desalinated water. They produce pure water for many applications. The combination of the Protegra CS RO with the EDI-cell significantly increases the pure water quality.

The compact design with high-quality components and intelligent control places great emphasis on cost-effectiveness. The plant systems are characterized by a consistent pure water quality. Conductivities of <0.1 µS/cm in single-phase and <0.07 µS/cm in dual-phase systems are achieved. The TOC content is < 30 ppb.

Germ reduction is achieved by means of the special arrangement of the separate bed process and a related pH-value shift into the acidic range, preventing the growth of bacteria in work spaces. No system operates more efficiently and economically, since the EDI-cell has a loss rate of only 10%. Low operating costs and a minimal maintenance outlay are features of this system.

These systems can be individually equipped with additional options such as different tank sizes and pressure boosting systems. They represent the core element in central water treatment plants in buildings and are used with the options necessary for a ring main operation. All systems have a RS 232 interface. Degassing systems to reduce the CO2 content in feed water are available – they ensure that the system remains within feed water specifications and protect the EDI-cell.

SPECIFICATIONS PROTEGRA CS RO/EDI, EDI-CELL SINGLE STAGE MODULE

Protegra CS RO EDI​120 Protegra CS RO EDI​​260 Protegra CS RO EDI​​500 Protegra CS RO EDI​​750
Delivery flow rate l/h 120 260 500 750
Pure water quality µS/cm <0.5 <0.5 <0.5 <0.5
Typical pure water quality µS/cm <0.1 <0.1 <0.1 <0.1
Max. yield % 75 75 75 75
Max. working pressure bar 14 14 14 14
Power consumption kW/h 0.6 0.75 1.5 1.7
​Power supply ​V / Hz 230 / 50​ ​230 / 50​ 230 / 50​​ 230 / 50​​
Dimensions H x W x D mm 1650 x 600 x 600 ​ 1650 x 600 x 750 ​
​Shipping weight ​kg 151​ ​165 ​237 ​291
Item code W3T200007 W3T199823 W3T200009 W3T198152

SPECIFICATIONS PROTEGRA CS RO/EDI, EDI-CELL TWIN STAGE MODULE

Protegra CS RO EDI​​120 Protegra CS RO EDI​​260 Protegra CS RO EDI​​500 Protegra CS RO EDI​750
Delivery flow rate l/h 120 260 500 750
Pure water quality µS/cm <0.1 <0.1 <0.1 <0.1
Typical pure water quality µS/cm <0.07 <0.07 <0.07 <0.07
Max. yield % 75 75 75 75
Max. working pressure bar 14 14 14 14
Power consumption kW/h 0.6 0.75 1.5 1.7
​Power supply ​V / Hz 230 / 50​ 230 / 50​​ 230 / 50​​ ​230 / 50​
Dimensions HxWxD mm 1650x600x600 ​ 1650x600x750 ​
​Shipping weight ​kg 155​ ​170 ​290 ​370
Item code W3T199822 W3T199619 W3T200008 W3T197525

PROTEGRA CS RO/EDI

Protegra CS RO EDI​​120 Protegra CS RO EDI​​260 ​Protegra CS RO EDI​500 Protegra CS RO EDI​​750
Feed water specifications
Pressure bar 1-5 1-5 1-5 1-5
Conductivity µS/cm 1400 1400 1400 1400
Silt density index SDI <3 <3 <3 <3
Free Chlorine mg/l 0.5 0.5 0.5 0.5
Total iron mg/l < 0.1 < 0.1 < 0.1 < 0.1
Silicate mg/l < 15 < 15 < 15 < 15
CO² mg/l < 15 < 15 < 15 < 15
Temperature °C 5-35 5-35 5-35 5-35
Water hardness °dH 0 0 0 0

This specifications are for single and twin-stage systems